What is a transformerless inverter
A transformerless inverter, also called TL inverter, is a solar inverter that omits the galvanic isolation transformer found in older inverter designs. Instead, the inverter uses high-frequency PWM switching, an LCL output filter and dedicated protection circuits to interface the PV array directly with the AC grid.
The transformer removal eliminates 2 to 4 percent of conversion losses (transformer copper and core losses), raising peak inverter efficiency to 97-98.6 percent for modern designs; see transformerless vs transformer-based solar inverters for a side-by-side breakdown. The inverter also becomes 30 to 50 percent lighter and 20 to 40 percent cheaper than equivalent transformer-isolated designs.
The trade-off is the absence of galvanic isolation between PV DC and AC grid. This requires Type B RCCB for fault current detection, PV insulation monitoring (Riso test on startup) and a floating (ungrounded) PV array configuration instead of conventional earthing. Modern transformerless inverters from major brands meet all relevant safety standards.
Why transformerless matters
Higher efficiency. 2 to 4 percentage points better than equivalent transformer-based designs.
Lower cost. Smaller bill of materials, less copper, less iron.
Lighter weight. Easier installation, lower shipping cost.
Smaller footprint. Wall-mount installations easier.
Industry standard. Almost all modern Indian solar inverters are transformerless.
How transformerless works
A typical transformerless inverter has these stages:
- PV input with isolation monitor (Riso test).
- Boost converter to raise PV voltage to DC bus level.
- H-bridge or multi-level inverter switching at 16-50 kHz PWM.
- LCL filter smoothing chopped output to clean sine wave.
- Direct AC connection to grid through contactor.
Compared to transformer-isolated designs, the omitted line-frequency transformer would have provided 50 Hz galvanic isolation. Without it, the inverter’s safety design must include ground fault detection (Type B RCCB), PV insulation monitoring, and common-mode current control - the same core process our how does a solar inverter work guide covers stage by stage.
Technical deep dive
Common transformerless topologies
| Topology | Origin | Efficiency | Notes |
|---|---|---|---|
| H5 | SMA | 97% | Single-phase, 5 switches |
| H6 | Various | 97% | Single-phase, 6 switches |
| HERIC | Sunways | 98+% | Highly Efficient and Reliable Inverter Concept |
| NPC (Neutral Point Clamped) | 3-level | 98-99% | Three-phase, central inverters |
| T-type | 3-level | 98-99% | Three-phase, lower component count |
| Active NPC | Improvement | 99% | Premium efficiency |
| Modular Multilevel | Emerging | 99% | Very large utility |
Required safety circuits
| Circuit | Function |
|---|---|
| Riso (Insulation Resistance) | Test PV array insulation before connecting |
| Residual Current Detection (RCD) | Type B for DC + AC leakage detection |
| Ground fault interrupter | Trip on DC ground fault |
| Common-mode filter | Reduce capacitive leakage |
| Isolation monitor | Continuous PV-to-ground impedance check |
Efficiency comparison
For the full context on why each percentage point of efficiency matters over a 25-year system life, see solar inverter efficiency explained.
| Topology | Peak efficiency | European weighted |
|---|---|---|
| Line-frequency transformer | 94-96% | 92-94% |
| High-frequency transformer | 95-97% | 93-95% |
| Transformerless H5/H6 | 97-98.6% | 96-98% |
| Transformerless HERIC | 98+% | 97-98% |
| Multi-level transformerless | 98-99% | 97-99% |
Real-world applications
Indian residential rooftop solar.
C&I rooftop solar string inverters.
Utility-scale string inverters.
Central inverters with external step-up transformer.
Hybrid inverters for solar-plus-storage, where correctly sizing the battery bank alongside the transformerless front end determines usable backup.
Advantages
Highest efficiency among inverter topologies.
Lower cost than equivalent transformer-isolated.
Lighter and smaller footprint.
Mature technology with wide market availability.
Standardised safety design.
Limitations
No galvanic isolation requires special protection.
Type B RCCB more expensive than Type A.
PV array must be floating (not directly earthed).
Common-mode current filtering required.
Cannot directly support systems requiring isolation (e.g., medical).
Common transformerless problems
Riso test failure on startup due to moisture on PV cables.
Type B RCCB nuisance tripping from accumulated capacitive leakage.
Insulation monitor false positives during heavy rain.
Ground fault detection requiring inverter shutdown for resolution. See solar inverter ground fault error troubleshooting for the full diagnostic sequence.
Best practices
Use Type B RCCB rated for solar DC leakage.
Specify minimum Riso threshold per inverter datasheet.
Use PV cable with adequate insulation rating.
Maintain dry PV junction boxes.
Verify floating PV configuration during commissioning.
Indian market context
Major brands (Sungrow, Solis, Goodwe, Growatt, Solax, Deye, Tata Power Solar) ship transformerless residential and C&I inverters, and ready-stocked units are also available through Heaven Green Energy’s solar inverter catalogue.
Utility central inverters from Sineng, Huawei, Sungrow use transformerless multi-level topology.
PM Surya Ghar residential installations use transformerless string inverters universally.
The CEA connectivity regulations and inverter safety standards such as IEC 62109 accommodate transformerless designs.
Standards and certifications
| Standard | Scope |
|---|---|
| IEC 62109-2 | Particular requirements for inverters |
| IEC 61727 | Utility interface |
| CEA Connectivity Regulations 2013 (as amended 2019) | Grid connection of distributed generation |
| IS 16221 | Indian inverter safety |
Further reading
For how Transformerless Inverter plays out in real projects, these guides go deeper:
Sources
- IEC 62109-1, -2, Inverter safety.
- IEC 61727, Utility interface characteristics.
- CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations, 2013 (as amended 2019), Central Electricity Authority.
- SMA HERIC and H5 patent documentation.
- Teodorescu R., Liserre M., Rodriguez P., Grid Converters for Photovoltaic and Wind Power Systems, Wiley-IEEE.
- NREL Power Electronics for Photovoltaic Systems.
- Manufacturer documentation from Sungrow, Solis, Goodwe.
- ITRPV Roadmap, latest edition, VDMA.
- IEA PVPS Task 14 publications.
Apply this term
Frequently Asked Questions
What is a transformerless inverter in simple words?
Why is transformerless better?
What is the downside?
What topologies are transformerless?
Is transformerless ALMM-listed?
Are transformerless inverters safe?
Do transformerless inverters need special earthing?
Are central inverters transformerless?
Is HERIC topology transformerless?
Why do older inverters use transformers?
Are microinverters transformerless?
Does transformerless affect EMC?
What is leakage current?
Are transformerless inverters used in utility plants?
What is the cost premium?
From the Blog
Listed by Qbits as its CTO. Current role, technical responsibilities and credentials require confirmation by the company owner.