What is THD?
Total Harmonic Distortion (THD) compares the combined RMS magnitude of harmonics with the RMS magnitude of the fundamental component in an electrical waveform. It can describe voltage or current. A solar-inverter datasheet commonly gives an AC-output current THD figure, but the load and test conditions matter.
A lower THD figure can indicate a cleaner waveform under the same measurement method. It is not a complete statement about grid compliance, equipment safety or performance at every output level.
A perfect sine wave has a THD of zero. An ideal square wave works out to about 48 percent, dominated by the 3rd, 5th and 7th harmonics. Real supply voltage and real inverter output sit between those extremes.
THD explained simply
Think of a single clean musical note. On the Indian grid that note is the 50 Hz fundamental. Now add several faint, higher notes at 150 Hz, 250 Hz, 350 Hz and so on. Each one is a harmonic, an exact whole-number multiple of 50 Hz. The waveform is no longer a pure tone, and THD is the single number that says how large those extra tones are compared with the main one.
Harmonics are produced by non-linear loads and by switching electronics, including rectifiers, variable-speed drives, LED drivers and inverters. A solar inverter produces its output by high-frequency switching and then filters it, so the remaining distortion depends on the filter, the control loop and the operating point.
Formula and checked example
For harmonic components numbered 2 through n:
Here each H is the RMS magnitude of that frequency component, and H₁ is the fundamental. The same form is used for voltage (V) and current (I). IEEE 519-2014 counts harmonic orders up to the 50th.
A real analyser may include more harmonic orders and apply a specific aggregation method. Its reported value can therefore differ from a simplified hand calculation.
Total demand distortion (TDD)
IEEE 519-2014 defines TDD as the RMS of the harmonic current content (orders up to 50, excluding interharmonics) divided by the maximum demand load current I_L, expressed as a percentage. Because I_L is a fixed reference rather than the current at the moment of measurement, TDD does not balloon at light load the way current THD can. It is the quantity IEEE 519 uses for current limits at the point of common coupling.
Voltage THD, current THD and TDD
| Measure | Numerator | Denominator | Common use |
|---|---|---|---|
| Voltage THD | Voltage harmonics | Fundamental voltage | Describes voltage waveform distortion at a measurement point |
| Current THD | Current harmonics | Fundamental current at that operating point | Describes current distortion under the stated load |
| Current TDD | Current harmonics | Defined maximum demand load current | Helps assess harmonic impact against a demand reference |
Voltage and current distortion are linked through the network. A harmonic current I_h flowing through grid impedance Z_h at that harmonic frequency produces a harmonic voltage drop of roughly Z_h × I_h. A weak grid, with high impedance, turns the same inverter current into more voltage distortion than a strong grid does.
THD-F and THD-R
Two definitions are in use. THD-F (also called THD of the fundamental) divides the harmonic RMS by the fundamental RMS, as above, and is the usual engineering and standards definition. THD-R divides by the total RMS value including harmonics, so it is capped at 100 percent. At low distortion the two are almost identical, but they diverge as distortion grows. Some instruments default to THD-R, so check the definition in the report before comparing numbers.
How THD is measured
A compliance-grade measurement follows a defined chain.
- Voltage and current are sampled at a high rate, over many samples per fundamental cycle.
- A Fourier transform extracts the magnitude and phase of each harmonic. IEC 61000-4-7 sets out the measurement method for harmonics and interharmonics.
- Values are aggregated over a defined interval. IEC 61000-4-30 describes power-quality measurement methods, including Class A instruments and a 10-minute aggregation interval for harmonics.
- THD (or TDD) is computed and individual harmonic magnitudes are reported where needed.
A quick handheld snapshot is useful for troubleshooting but is not equivalent to a Class A, aggregated measurement for a compliance report.
IEEE 519-2014 limits at the point of common coupling
IEEE 519-2014 is a recommended practice that sets limits at the point of common coupling (PCC), the point where the user connects to the utility. Voltage limits in Table 1 are:
| Bus voltage at PCC | Individual harmonic | Voltage THD |
|---|---|---|
| 1 kV and below | 5.0% | 8.0% |
| Above 1 kV to 69 kV | 3.0% | 5.0% |
| Above 69 kV to 161 kV | 1.5% | 2.5% |
| Above 161 kV | 1.0% | 1.5% |
Current limits (Table 2, for 120 V to 69 kV systems) are expressed as a percentage of I_L and depend on the ratio of short-circuit current to load current (I_SC/I_L). The TDD limit rises from 5% for a ratio below 20 to 20% for a ratio above 1000. Table 2 also states that power-generation equipment is limited to the lowest-ratio values (5% TDD) regardless of the actual ratio. Even-order harmonic limits are 25% of the odd-order limits. Check the standard itself for the order-by-order limits.
Reading an inverter specification
Check whether the figure covers rated output only, a range of loads, a stated power factor and a defined grid voltage. Also check the standard or procedure used for the measurement. A grid-connection decision should use the actual applicable utility and product documentation, not a single THD number copied from an article.
The Qbits datasheet library is the starting point for a specific inverter model. As an example of per-model differences, the published technical data (checked October 2026) for the QB-4.6/5/6KTLS single-phase family lists THD below 3% under rated power, while the QB 6 to 17KTLC three-phase datasheet lists THD below 2% under rated power. Both also state DC current injection below 0.5% under rated power. Quote the figure for the exact model and its stated condition, and do not carry one family’s number to another. For an engineering review, request the current model revision and its test report. If a site has a harmonic complaint, have a qualified person measure at the relevant point of connection; do not assume the inverter is the sole source when loads, transformers and other equipment share the network. The guide to THD in solar inverters covers how output filters and control affect the figure in practice, and the on-grid inverter range lists the Qbits models those datasheets belong to.
Where THD figures are used
- Inverter datasheets and type-test reports, usually as current THD at rated output.
- Grid-connection review, where the utility checks harmonic injection at the PCC for larger plants.
- Industrial supply contracts, which can stipulate voltage THD limits at the incomer.
- Power-quality audits of factories, data centres, hospitals and laboratories with sensitive loads.
- Harmonic studies for variable-speed drives, EV charging stations and capacitor-bank installations.
What THD does well, and where it falls short
THD is a single number that is easy to communicate, standardised and measurable with off-the-shelf analysers, and it correlates reasonably with equipment heating. Its limits are real, though. It reports magnitudes and says nothing about the phase relationship among harmonics. It does not capture interharmonics, which sit between whole-number multiples of the fundamental. It hides which harmonic order is the problem. It depends on the averaging window, so short windows can show transient spikes. And low-load current THD can mislead about the distortion at the typical operating point.
Common problems on site
- Higher THD at light load than at rated output, which is normal behaviour and often not a fault.
- High grid voltage THD before the inverter is even connected, which the inverter cannot fix and which may affect its operation.
- Resonance between a site capacitor bank and the network, which amplifies one harmonic order. Agricultural and mixed industrial feeders with switched capacitors are a typical setting.
- Measurement artefacts from low-quality current or voltage transformers, or from comparing a THD-F figure with a THD-R figure.
- Triplen harmonics (3rd, 9th, 15th) adding in the neutral of a three-phase four-wire system.
Practical steps
- Ask for current THD at rated load and at light load when comparing inverter offers.
- For compliance measurement, use a Class A analyser and aggregated values, not an instantaneous reading.
- Check for resonance risk before adding or switching capacitor banks.
- Log THD at maintenance visits. A rising trend can point to filter or capacitor ageing.
THD compared with related metrics
| Metric | Definition | Typical use |
|---|---|---|
| THD-F | Harmonic RMS ÷ fundamental RMS | Standard engineering and datasheets |
| THD-R | Harmonic RMS ÷ total RMS | Default on some instruments |
| TDD | Harmonic current RMS ÷ maximum demand current | IEEE 519 current limits at the PCC |
| Interharmonics | Components at non-integer multiples of the fundamental | Specialised analysis |
| Crest factor | Peak ÷ RMS | A different view of waveform shape |
Indian context
India’s central connectivity rules for distributed generation below 33 kV are the CEA technical standards (Technical Standards for Connectivity of the Distributed Generation Resources Regulations, 2013, as amended; the 2019 amendment inserted Regulation 11A). Regulation 11 says harmonic current injection from a generating station must not exceed the limits in IEEE 519, and that a distributed generating resource must not inject DC greater than 0.5% of its full rated output at the interconnection point. Regulation 11A says harmonic injection limits at the point of common coupling and the measurement method follow IEEE 519-2014, that harmonics are to be measured continuously with power-quality meters complying with IEC 61000-4-30 Class A, and that users connected at 11 kV or above install such meters. Harmonic current, DC injection and flicker are measured with calibrated meters before commissioning. Check the CEA publication for the current text and for any newer amendment, and check your DISCOM’s commissioning checklist, because states and utilities add their own procedures.
Be careful with a few claims that circulate. There is no single Indian inverter THD figure that every product is certified to, and a BIS or other certificate does not by itself state a THD value. IS 17387 is a standard for battery management systems, not a solar inverter THD standard. ALMM, which MNRE publishes for modules and cells, says nothing about inverter THD.
Standards and references
| Standard or document | What it covers |
|---|---|
| IEEE Std 519-2014 | Recommended practice and requirements for harmonic control in electric power systems |
| IEC 61000-4-7 | Measurement of harmonics and interharmonics |
| IEC 61000-4-30 | Power-quality measurement methods |
| IEC 61000-3-2, 61000-3-12 | Emission limits for equipment connected to public low-voltage networks |
| CEA Technical Standards for Connectivity of the Distributed Generation Resources Regulations, 2013 (as amended, including Regulation 11A) | Indian connectivity requirements below 33 kV: harmonics per IEEE 519, DC injection, flicker, Class A power-quality metering |
Sources: IEEE 519-2014 summary of limits; CEA regulations on connectivity of distributed generation resources (CBIP copy, consolidated with the 2019 amendment). Checked 14 October 2026.
Common mistakes
- Quoting THD only at rated load and ignoring light-load behaviour.
- Mixing up THD-F and THD-R.
- Looking only at total THD and skipping the individual harmonic limits.
- Using an instantaneous snapshot where an aggregated Class A measurement is required.
- Comparing THD figures taken under different test conditions or standards.
- Ignoring grid-side voltage THD when judging inverter behaviour.
Key takeaways
THD is the headline metric for waveform distortion, but it only means something when the quantity (voltage or current), the load point and the method are stated. Standards judge harmonics at the point of common coupling, mostly through TDD for current and voltage THD for the supply. Light-load current THD is usually higher and should be checked at design stage. Related terms to read next: power factor, performance ratio and the safety scope of IEC 62109.
Frequently Asked Questions
What is THD in simple terms?
What is the THD formula?
Is THD the same as TDD?
Does a datasheet THD figure apply at every load?
Is THD a voltage or a current measure?
What voltage THD limit does IEEE 519-2014 set?
Does IEEE 519 apply to a solar inverter by itself?
How is THD measured?
What is the THD of a square wave?
Can THD ever be zero?
What is the difference between THD-F and THD-R?
Does high THD damage equipment?
Why can THD be high at low inverter output?
Can two inverters on one feeder cause a harmonic problem together?
Where do I find the THD figure for a Qbits inverter?