Solar string sizing checks whether a proposed series and parallel module arrangement stays within an inverter’s voltage, current and MPPT limits across the design temperatures. Use the exact module and inverter documents, declare the site-temperature basis, keep units visible and have a qualified designer verify the result. A generic panel count is not a design.
This guide covers the calculation structure. It does not prescribe a universal safety factor, fuse rule or Indian temperature value because those inputs depend on the controlling documents and project requirements.
Which documents and inputs are needed first?
Collect the exact module datasheet, inverter datasheet and manual, approved design temperatures, array layout and applicable protection requirements before calculating. Record document revisions and units. Closely related equipment variants can have different voltage, current, connector and MPPT limits, so a brand or family name is insufficient.
Use this input sheet:
| Input | Symbol | Unit | Source |
|---|---|---|---|
| Module open-circuit voltage at stated conditions | Voc | V/module | Exact module datasheet |
| Module maximum-power voltage | Vmp | V/module | Exact module datasheet |
| Module short-circuit current | Isc | A/string | Exact module datasheet |
| Module maximum-power current | Imp | A/string | Exact module datasheet |
| Voltage temperature coefficients | βVoc, βVmp | fraction/°C or %/°C | Exact module datasheet |
| Design minimum and maximum cell temperatures | Tmin, Tmax | °C | Approved project basis |
| Inverter maximum DC voltage | Vdc,max | V | Exact inverter document |
| MPPT operating window and start-up voltage | Vmppt,min/max | V | Exact inverter document |
| Input and MPPT current limits | Imax, Isc,max | A | Exact inverter document |
| Number and architecture of independent trackers | MPPT count | count | Exact inverter document |
Convert percentage coefficients to fractional form before using them in a formula, or keep the percentage calculation explicit. Do not mix ambient and cell temperature without an approved model.
How is cold-weather open-circuit voltage checked?
Correct module Voc to the approved minimum cell temperature, multiply by the number of series modules, and compare the result with the inverter’s absolute DC limit. Use the sign and units printed by the module maker. Apply any additional design margin only when its source and scope are documented.
For a coefficient expressed as a fraction per degree Celsius:
Because many module Voc coefficients are negative, a minimum temperature below the reference temperature normally raises the calculated Voc. The formula still needs the module maker’s exact coefficient and the project’s approved cell-temperature basis.
Do not use an assumed “India uplift.” A hill site, desert site and coastal site do not share one design minimum, and site elevation or local records can matter.
How is hot operating voltage checked against the MPPT window?
Correct module Vmp to the approved maximum cell temperature, multiply by the series count and compare it with the applicable MPPT operating requirement. The check asks whether the inverter can track the string under hot operating conditions. It is different from the cold absolute-voltage check and from start-up voltage.
The worksheet structure is:
Some inverter documents qualify the MPPT window by output level or input condition. Use the curve or note that applies to the proposed model rather than treating one printed range as a promise of full power everywhere within it.
How are input current and parallel strings checked?
Current checks are performed per physical input and per MPPT using the proposed parallel arrangement. Series modules raise voltage but do not add string current; parallel strings add current. Compare both operating-current and short-circuit-current totals with the exact inverter limits and the project protection design.
Record:
- How many strings land on each input.
- Which inputs share an MPPT internally.
- Module Imp and Isc at the stated basis.
- Any applicable current adjustment and its source.
- Input-connector and conductor limits.
- Reverse-current and overcurrent-protection requirements.
A connector count does not establish the number of independent trackers. The single versus dual MPPT guide explains why tracker architecture and roof allocation must be checked together.
What does a model-specific string-sizing screen look like?
A model-specific screen begins with published inverter fields, then stops where module or site inputs are missing. For the Qbits QB-4/5/6KTLD family, the current public datasheet lists two MPPTs, 550 V maximum DC, an 80–550 V MPPT range and 20 A maximum input current per MPPT.
Those fields do not produce a valid panel count by themselves. Complete this model screen with the proposed module and site data:
| Check | Published QB-4/5/6KTLD field | Missing project input | Status |
|---|---|---|---|
| Cold series voltage | 550 V maximum DC | Module Voc, βVoc, Tmin and series count | Pending calculation |
| Hot operating voltage | 80–550 V MPPT range | Module Vmp, βVmp, Tmax and series count | Pending calculation |
| MPPT allocation | Two independent MPPTs | Roof groups and strings per tracker | Pending layout |
| Input current | 20 A per MPPT | Module Imp/Isc and parallel strings | Pending calculation |
This is deliberately incomplete until an actual module and temperature basis are supplied. The published TLD datasheet controls the inverter fields, and the module document controls the remaining electrical inputs.
What should the calculation record contain?
Keep the original inputs, formulas, units, intermediate values and pass criteria with the design record. A screenshot showing only “pass” cannot reveal a stale database, coefficient-unit error or wrong model selection. The final record should allow another engineer to reproduce every result.
Include:
- Exact module and inverter identifiers and document revisions.
- Temperature source and whether values are ambient or cell temperature.
- Coefficient sign and conversion from percent where applicable.
- Proposed series count and parallel allocation per MPPT.
- Cold Voc, hot Vmp, operating current and short-circuit-current checks.
- Additional margins or protection rules with their controlling source.
- Design reviewer, date and approved result.
Use the Qbits string-sizing calculator as a screen, then compare its stored data with the current documents. The calculator does not replace protection coordination or engineering approval.
Which common errors invalidate a string calculation?
A calculation is invalid when it uses the wrong equipment variant, mixes temperature definitions, ignores coefficient units or tests only one electrical limit. Other frequent errors include treating start-up voltage as the MPPT minimum, adding parallel current incorrectly and assuming each connector is an independent tracker.
Also reject a calculation that:
- Uses a typical module instead of the quoted module.
- Uses a city temperature without an approved design basis.
- Omits cold Voc or hot Vmp.
- Compares Imp with an Isc limit or the reverse without explanation.
- Ignores per-input limits while checking only a total inverter limit.
- Applies an unexplained fixed multiplier.
- Has no versioned output after a module or inverter substitution.
The inverter datasheet guide provides a second check on voltage and current fields.
What should happen before procurement or installation?
Freeze the exact module, inverter, string allocation and calculation revision before equipment is ordered or connected. Re-run the calculation after any substitution, firmware-dependent input change or layout revision. Then align the labels, drawings, protection schedule and commissioning plan with the approved result.
Download current Qbits datasheets or request model-specific documents before final design. Electrical design and installation must be completed by qualified parties under the applicable project and local requirements.
Qbits inverters for this guide
Specs below come from each model's datasheet. Confirm the exact model and current written terms with Qbits before you buy.
QB 1.5/2.0/2.7/3.0/3.3/3.6/4.0KTLS
- Power
- 1.5–4 kW
- Phase
- Single-phase
- MPPT
- Single-MPPT
QB 4.2/4.6/5/5.4/6KTLS
- Power
- 4.2–6 kW
- Phase
- Single-phase
- MPPT
- Single-MPPT
QB 5/6/8/10/12/15/17KTLC
- Power
- 5–17 kW
- Phase
- Three-phase
- MPPT
- Dual-MPPT
Frequently Asked Questions
What inputs are needed for solar string sizing?
How is maximum string length checked?
How is minimum string length checked?
How many parallel strings can connect to one MPPT?
Can a string-sizing calculator approve a design?